iXPERT11 /31 series (6~20KVA) high frequency online UPS is fully DSP controlled high end online double conversion UPS which features with small footprint, light weight, high reliablity and high efficiency. It adopts DSP control, high efficient half bridge inverter, advanced hardware current limit technology. iXPERT 11/31 series provide perfect Sine wave output which can offer complete protection for critical load of small and medium business.
Fully DSP controlled
Online double conversion
Small footprint, light weight, high reliability
High efficiency up to 93%
Set charging current, output voltage from LCD
High input power factor
Wide input voltage range
50/60HZ source auto detection
Input surge protection (D class)
ECO mode for energy saving
Intelligent periodic battery charge and discharge, to prolong battery life
Input neutral and live wire reverse detection, to avoid reverse connection
Bypass output protection to protect the load
3 units parallel directly
Intelligent fan speed regulation
Fan fault detection and alarming
Intelligent real time monitoring, instantly alarm and start full protection
Self-diagnose when starting
DC cold start
Auto restart when AC source recover
Large LCD display and LED indication
Abundant options
SNMP card/USB/Parallel card
Model | iXPERT1106 /iXPERT1106L | iXPERT1110 /iXPERT1110L | iXPERT3110L | iXPERT3115L | iXPERT3120L | |
Capacity(KVA/KW) | 6/4.8 | 10/8 | 10/8 | 15/12 | 20/16 | |
Input | ||||||
Main input | Nominal voltage(Vac) | 220 | 380 | |||
Voltage range(Vac) | 120~275 | 207~475 | ||||
Phase | single phase three wire(1L+N+PE) | three phase five wire(3L+N+PE) | ||||
Frequency range(Hz) | (46~54)/(56~64)auto detection | |||||
Input power factor | >0.99 | >0.95 | ||||
Bypass input | Nominal voltage(Vac) | 220 | 380 | |||
Voltage range(Vac) | 187~273 | 302~437 | ||||
Phase | single phase three wire(1L+N+PE) | three phase five wire(3L+N+PE) | ||||
Bypass tracking(Hz) | ±10% | |||||
Output | ||||||
Voltage(Vac) | 220(200,208,230,240 setting) | |||||
Load Power factor | 0.8 | |||||
Frequency(Hz) | Normal mode: synchronizing with AC input, Battery mode: 50/60Hz | |||||
Wave Form | THD<2% (linear load); THD<5% (nonlinear load) | |||||
Transfer time(ms) | 0 | |||||
System efficiency | >93% | |||||
Overload | 105%~125%: 60s; 125%~150%: 30s; >150%: 0.5s | |||||
Battery | ||||||
Battery voltage(Vdc) | 192Vdc | |||||
Charger current | Stand type: 2A,Long backup time type: 1A/2A/4A setting | |||||
Backup time | Stand type: 16×12V7AH, Long backup time type: Depends on the capacity of external batteries | |||||
Environment | ||||||
Operating temperature(℃) | -10~40 | |||||
Storage temperature(℃) | -25~55(battery excluded) | |||||
Humidity range | 0~95%(no condensing) | |||||
Operating altitude | <1500m | |||||
Noise(dB) | <50 | <55 | ||||
Other Characteristic | ||||||
Alarm function | Overload, main fault, UPS fault, battery voltage low, etc | |||||
Protection function | short circuit, overload, overheat, battery voltage low, output voltage low&high, fan fault | |||||
Communication interface | standard: RS232 optional: SNMP/Dry contact/Parallel card/USB | |||||
Physical | ||||||
Dimension(W×D×H)mm | 248*500*616/195*455*330(L) | 195*455*330 | 240*500*460 | |||
Net weight(kg) | 57/14(L) | 58/16(L) | 17 | 27 | 27 | |
Standards | YD/T1095-2008 |